Bài giảng Tối ưu hóa vận hành hệ thống điện - Chapter 8: Control Of Generation - Võ Ngọc Điều

(Bản scan)

The isochronous governor • to force frequency errors to zero requires the use of an

integration of the speed error • the isochronous governor can not be used when two or more generators are electrically connected to the same system • fighting between generator governors for system frequency

• problems with load distribution between generators A load reference control provides settings for both the frequency and the desired output power • a new input, the load reference signal, controls the desired

power output • feedback loop contains a gain R that determines a speed-droop

characteristic

 

pdf33 trang | Chuyên mục: Hệ Thống Điện | Chia sẻ: tuando | Lượt xem: 542 | Lượt tải: 1download

File đính kèm:

  • pdfbai_giang_toi_uu_hoa_van_hanh_he_thong_dien_chapter_8_contro.pdf
Tài liệu liên quan